• https://www.rmuswitchgear.com/wp-content/uploads/2021/03/11kv-sf6-load-break-switch-570.jpg

11kV SF6 Load Break Switch

11KV sf6 load break switch refers to international new technology and develops the switching equipment according to the relevant standards in China’s electric power system.

Its performance indicators in full compliance IEC420,694,129 and national standards GB3804-2004“3.6kV-0.5kV high voltage  AC load breaker switch” GB1985-2004“high-voltage AC isolation switch and earthing switch”, GB/ T11022-1999“ common technical requirements for high-voltage switchgear and control equipment standards“,  This is the main switching element RMU.

The load breaker switch is a collection of multifunctional medium voltage switchgear of gates,sub-gate, earthing.  In a fully sealed with strengthening the structure of the epoxy resin housing to filled with SF6 gas,0.05MPa, with the minimum parts to achieve the above three functions, to ensure product quality, improve reliability, maintenance-free.  It can be safely run for more than 20 years in normal conditions.

1.Load breaker switch adapts double fracture, rotary movable contact structure, with the following three kinds of operating states: Closing, opening, earthing.

2.Using SF6 gas as an arc extinguishing and insulating medium, the main circuit seals by the upper and lower housing pouring epoxy resin.
The conductive function is unaffected by external influences.

3.Good safety performance. If internal arcing occurs, the housing has an internal structure weak point, it will be rushed to open, followed by the cabinet above the shutter release arc red open-air overpressure stream-oriented outside the cabinet, ensure that the switch cabinet security checks.

4.Load breaker switch sets gates, opening, earthing switch three at once, filled with SF6 gas encapsulated in epoxy resin housing, three-position interlock, compact structure, high security, and reliability.

5.small size, lightweight, maintenance-free, easy, and safe to operate.

 

Normal working Environment

 

  1. Altitude: ≤1000m
  1. The ambient temperature at -30℃ to +40℃, the daily average temperature should not more than 30℃.
  1. The daily average of relative humidity is less than 95%, the average monthly is less than 90%.
  1. The working environment should be without steam, gas, chemical corrosive deposition, salt fog, dust, dirt, and other dangerous explosive media, which will severely impact on insulation and conductivity of products.
  1. The working environment should not be regular vibration or serious bumps.
 Item UnitData
Rated voltageKV12
Rated frequencyHz50
Rated currentA630
Rated peak withstand currentKA50
4s rated short-time withstand currentKA20
Rated making currentKA50
Rated breaking current Active load breaking current630
Breaking current loopA630
Cable charging breaking currentA10
1min power frequency withstand voltage (phase to phase, to earth, fracture)KV42/48
Lightning impulse withstand voltage (phase to phase, to earth, fracture)KV75/85
Relative pressure of SF6 gas (20℃ GP)MPa≤0.04
Rated operating voltage (electric)VAC220,DC220
Rated voltage of shunt releaseVAC220,DC221
Average opening speedM/S3.5±1.5
Average closing speedM/S3.5±1.6
Three-phase points, dosing phase of the samems≤3
The main circuit resistanceμΩ≤120
Manual maximum torqueN.m≤160
Phase to phase center distancemm210±0.5

11kv sf6 load break switch drawing

CEO Note

Hey! This is Tony, the CEO of Jihui Electric Group. Thanks for visiting our website and I hope to be a friend with you. I have 20 years experience in electric power transmission for primary distribution and secondary distribution, I would like to share my experience with you in this field, please contact me to discuss when you have any question about our products, I’m happy to help you. I provide free consultant for many clients, and if you need any help on power transmission, reach me any with with blow button.

Related Products

Become An Expert When Importing Medium Voltage Electrical Equipments

Here will be the most detailed and professional basics focusing on electrical switchgear.
You could learn the ultimate guide to know the working principle of SF6 gas insulated switchgear from here.
Air circuit breaker and vacuum circuit breaker with the same function as breaking, but their big difference you must know to select the correct one for your project.
Here is the most comprehensive tips for you to know the difference between the power transformer and distribution transformer.
Scroll to Top